WELCOME TO OUR WEBSITE!中文站
Current Location:Home >PRODUCTS>HNPSE1000>HNP6000 Series SF6-O2 Gas Online Monitoring Alarm System

Products List

On-line+
HNPBL-1000
HNPDM-1802
HNPJF-1500B
HNPRT-18B
HNPRX-1000B
HNPRX-1000C
HNPSE1000
Portable+
A-B SF6

Contact Us

  • Phone:0519-83113788
  • Fax:0519-83113786
  • E-mail:hnppower@126.com
  • Address:400 Changshun Road, Wujin District, Changzhou
  • Products Name:

  • HNP6000 Series SF6-O2 Gas Online Monitoring Alarm System

    Overview

    Based on the current situation that the power system emphasizes safe production, the HNP series SF6-O2online monitoring alarm system is an intelligent online monitoring system designed and developed for providing personal health and safety protection for the staff who work in the distribution device room with SF6 equipment. It is mainly used to detect the content of SF6 gas and oxygen in the ambient air. When the content of SF6 gas in the environment exceeds the standard or if oxygen is lacking, the system can alarm in real time and automatically start the fan for ventilation at the same time. The system also has the functions such as temperature and humidity detection, working status voice prompt, remote alarm, GSM short message sending alarm messages (optional) and historical data query, etc.

    Its unique trace SF6 gas detection technology can detect the SF6 gas below 1000ppmv, which can not only ensure the personal safety, but also ensure normal operation of the equipment. The imported oxygen sensor with high stability can provide additional reliable protection for on-site staff.

    Schematic Diagram

    6.jpg

    Field Monitoring Software

    7.jpg

    Technical Parameters

    SF6 gas monitoring range

    0~1500ppmv

    SF6 gas measurement precision

    ≤50ppmv

    Oxygen monitoring range

    0~25%

    Oxygen measurement precision

    <0.4%

    SF6 gas alarm point

    1000ppmv or can be customized by users

    Oxygen lacking alarm point

    18% or can be customized by users

    Temperature display range

    -50~99°C

    Humidity display range

    0~99%RH

    Working power supply

    AC 220V/50Hz

    Alarm output point current

    2A

    Fan output point current

    16A

    Fan ventilation time

    15min or settable

    Communication protocol

    RS485/IEC61850

    Historical record capacity

    >500 alarm records

    Main display characteristic

    800×480 TFT touch screen